2.32 Over Voltage Protection / Low Voltage Protection

U2
Remote
Controller Display
Method of
Detect an abnormal increase or drop of voltage by the over voltage detection circuit or DC
voltage detection circuit.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Service Diagnosis
When an over voltage signal is sent to the microcomputer from the over voltage detection
circuit, or the voltage detected by DC voltage detection circuit is less than 150 V and that
voltage continues for about 0.1 second.
The unit shuts down if the fault conditions occurs repeatedly.
Fault counter is reset when the unit continuously runs for 11 minutes without fault.
Abnormal supply voltage, momentary power failure
Defective over voltage detector or defective DC voltage detection circuit
Failure in PAM controlled parts
Short circuit inside the fan motor winding.
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Check the supply voltage.
Supply voltage as
specified?
YES
Rotate fan by hand.
Does fan rotate
smoothly?
YES
Turn on the power
again. System
restarted?
NO
Repeat a
couple of times.
NO
NO
(Precaution before turning on the power again)
Make sure the power has been off for
at least 30 seconds.
YES
Disturbance factors
∗ Noise ∗ Power supply distortion
Troubleshooting
Correct the power supply.
Replace fan motor and
outdoor unit PCB.
Check for such factors for a
long term.
∗ Try to get restarted a
couple of times.
Replace the outdoor unit
PCB.
(R9451)
156