Panasonic S-45PU1E5 Technical Data & Service Manual page 369

Table of Contents

Advertisement

(B) If there are obstacles at the discharge
If the upper part is open
For separate installation location
1
If there are obstacles above the unit
For separate installation location
1
(C)
If there are obstacles on both the intake and discharge
If there is an obstacle that is higher than the unit on the intake side.
Pattern 1
(There is no limit to the height of the obstacle above the discharge.)
If the upper part is open
For separate installation location
1
If there are obstacles above the unit
For separate installation location
1
• The dimensions for H, A and L are shown in the following table.
0 < L 1/2 H
L H
1/2H < L
H < L
Install a pedestal or mount so that L H
• Cover the bottom part of the pedestal or mount
so that air does not go through it.
For multiple units (up to 2 units)
2
• The dimensions for H, A and L are shown in the following table.
0 < L 1/2 H
L H
1/2H < L
H < L
Install a pedestal or mount so that L H
• Cover the bottom part of the pedestal or mount
so that air does not bypass it.
• A limit of only 2 units can be installed.
L
A
300
H
500
L
A
500
H
750
For multiple units (more than 2 units)
2
For multiple units (more than 2 units)
2
For multiple units (more than 2 units)
2
1-359
1
(unit: mm)
(unit: mm)
(unit: mm)
(unit: mm)