Panasonic S-45PU1E5 Technical Data & Service Manual page 346

Table of Contents

Advertisement

1
Test Run Procedure
Turn ON the indoor
and outdoor power.
Automatic Address Setting
Recheck the items to check before the test run.
Check the combination (wiring) of indoor and outdoor units.
YES
Is system "single-type"?
Is outdoor unit multiple?
(See section "Setting outdoor unit system addresses"
for U1, T1, F1, N1 Types (for Link Wiring).)
How to Set the Outdoor Unit System Address
Set the outdoor unit system address.
(See section "Basic wiring diagram"
for U1, T1, F1, N1 Types (for Link Wiring).)
How to Set Automatic Address
Set the automatic address setting from
outside unit or remote controller.
(*) Indicate (mark) the combination number.
(See section "Checking indoor unit addresses" and "Indicating (marking) the indoor
and outdoor unit combination number" for U1, T1, F1, N1 Types (for Link Wiring).)
Turn ON the indoor and outdoor power. (Automatic Address Setting)
Set the remote controller to "test run".
Can operation
be started?
Return the remote controller
to normal control.
NO
NO
YES
See section "Test Run Using the Remote
Controller" for U1, T1, F1, N1 Types
(for Link Wiring).
See section "Table of Self-Diagnostic Functions
and Corrections (U1, T1, F1 N1 Types)"
Refer to "Table of Self-Diagnostic
NO
Functions" to check the system.
In addition, refer to section "Automatic
Address Setting" for U1, T1, F1, N1 Types
(for Link Wiring) and correct any items that
YES
need to be corrected.
Note: Check the indoor side drainage.
(*)
Required for simultaneous-operation
multi systems and for group control.
1-336
See section "Items to Check Before the
Test Run" for U1, T1, F1, N1 Types
(for Link Wiring).
See section "Basic wiring diagram"
for U1, T1, F1, N1 Types
(for Link Wiring).