Installation
  Installation of Strainer (Field supplied)
Attach the strainer to the side of the outdoor unit for Gas & Liquid piping.
(See the "System Overview" on previous page.)
Thermistor for Liquid pipe and Heat exchanger pipe middle
Liquid pipe thermistor
Attach the liquid pipe thermistor
to the liquid pipe located in the
lowest position after distributer
in heat exchanger.
Heat exchanger pipe thermistor
Attach the heat exchanger
pipe thermistor in the middle
of each pass-line (pipe) in
the heat exchanger.
Attachment of NOTES Label (Supplied parts)
Please be sure to apply the NOTES label at the designated area of the outdoor unit when cutting a jumper
wire on the circuit board.
Cover the thermistor
and pipe with
aluminum tape.
Cover the thermistor
and pipe with
aluminum tape.
1-440
Cover the aluminum
tape with thermal
insulation.
The thermistor is fixed
in band.
Then, it must not make
tension to the wire.
NOTES
Thermal insulation and
wiring are fixed in two
bands.
Cover the aluminum tape
with thermal insulation.
And also cover sensor
(copper portion) with
thermal insulation completely.