H31 HIC Trouble
1.
Error Detection Method
It is judged an error if the computer detects an error signal from the HIC.
An error signal is issued by the HIC if abnormal heat occurs inside the HIC or if there is an overcurrent.
However, it is judged an error in the same way if the signal line from the HIC is not connected properly or opened.
HIC overcurrent due to HIC fault
HIC abnormal heat caused by defective HIC or HIC radiation error
Signal line is not connected properly or opened between the HIC and the
2.
Error Diagnosis
1 Wiring
The wiring (power cord and signal line) between the HIC
1-1
between
and the outdoor CR board is connected properly.
HIC &
Everything is normal in the wiring (power cord & signal line)
outdoor
between the HIC and the outdoor CR board. Check the
control
1-2
wiring one by one with a tester if there is opened and
PC board
grounding.
2
Check the
outdoor
The connector CN-PRY1 on the CR PC board is connected
2-1
unit CR
properly (locked). (3-phase only)
PC board
3
HIC poor
The heat dissipating surface on the back of the HIC is in
radiation
good contact with the heat sink (heat dissipating fins) of the
3-1
electrical box. Check for looseness in the fastening screws
and the condition of the heat-conducting putty.
A good flow of cooling air passes through the heat sink
3-2
(heat dissipating fins) of the electrical box.
Check for debris blocking the fins.
4 HIC
The results of the pass/fail tests for the following HIC board
overcurrent
4-1
IPM show it to be outside the range of the resistance of a
conforming part.
The inverter compressor was stopped/started more than 10
4-2
times and it triggered H31 at a high rate. If alarm code P16
occurs at times, refer to the alarm code P16.
HIC board IPM Pass/Fail Tests
Measure with an analog tester. (Set to the k ohm range)
Measure the board by itself. (Remove wires connected from other parts.)
Measure using IPM terminals.
Conforming part resistance value (measure with an analog tester)
Tester terminals
+
-
Resistance value (ohm)
Tester terminals
-
+
Resistance value (ohm)
Excepting the parts of "
value is "0 = short-circuit".
P
U
V
1 k to 5 k
1 k to 5 k
1 k to 5 k
P
U
V
100 k to
100 k to
100 k to
100 k to
", it is acceptable if a small resistance value appears as a reference value unless the
outdoor CR
W
NU
U
5 k to 10 k
100 k to
W
U
1 k to 5 k
5-41
board.
Yes
1-2
No
Correct wiring (connector)
3-1 : Single-phase model
Yes
2-1 : 3-phase model
No
Replace wiring
Yes
3-1
No
Correct wiring (connector)
Yes
3-2
Tighten screw(s),
No
add putty
Yes
4-1
No
Remove foreign matter
Yes
Replace the HIC PC board
No
4-2
Yes
Replace the HIC PC board
No
Refer to alarm code P16
N
U
V
W
100 k to
100 k to
100 k to
N
U
V
W
1 k to 5 k
1 k to 5 k
5