Panasonic S-45PU1E5 Technical Data & Service Manual page 498

Table of Contents

Advertisement

1
1-13. Capacity Table
2. Heating Capacity Performance Data
Combination of Single Unit
4-Way Cassette 60×60 Type
Power
Model
Source
220V
230V
S-50PY1E5
240V
U-50PE1E5
50Hz
1 phase
Ambient
Return
-5°C
Air
DB
TC
IPT
16
4.4
2.00
20
4.3
2.11
24
4.1
2.17
Outdoor air intake temp(°C W.B.)
0°C
6°C
TC
IPT
TC
IPT
4.7
2.06
6.5
4.6
2.17
6.3
4.4
2.23
6.0
1-488
TC
:Cooling Capacity
IPT :Cooling Power Consumption
10°C
TC
IPT
TC
2.44
8.0
2.92
2.57
7.8
3.08
2.65
7.5
3.17
unit : kW
15°C
IPT
8.5
2.80
8.3
2.95
7.9
3.04