Setting the outdoor unit system addresses
For basic wiring diagram 2 (Set the system addresses: 1, 2,...)
Outdoor unit control PCB
System address rotary switch
(Set to "0" at time of shipment)
System address rotary switch
System address
10s 20s
DIP switch
ON
ON
1
2
OFF
HIC
Temperature
sensor
Up side
C2(CN020,WHT)
MOV(CN025,WHT)
63PH(CN004,RED)
Bottom
side
Automatic address setting from the outdoor unit
When there are multiple outdoor units as shown in basic wiring diagram 2
If the power can be turned ON separately for the indoor and outdoor units in each system:
The indoor unit addresses can be set without running the compressor.
Be sure to use a jig for short-circuiting.
(1)
Turn ON the indoor and outdoor unit power for refrigerant system 1.
Short-circuit the AUTO ADD (CN041) pin for 1 second or longer at the outdoor unit where the power was
turned ON.
Communication for automatic address setting begins. LED 1 and 2 on the outdoor unit control PCB blink
alternately, and turn OFF when address setting is completed.
(2) Next, turn ON the power only at the indoor and outdoor units in a different system.
Short-circuit the AUTO ADD (CN041) pin for 1 second or longer on the outdoor unit.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
Repeat the same procedure for each system and complete automatic address setting.
(3) Operation using the remote controller is now possible.
0 Automatic address
1 (If outdoor unit is No. 1)
2 (If outdoor unit is No. 2)
11 (If outdoor unit is No. 11)
AUTO ADD(CN041)
System address
Rotary switch(S002)
TERMINAL (CN003)
JP007
21 (If outdoor unit is No. 21)
System address
DIP switch (S003)
RC-P(CN032,RED)
LED1
LED2
30 (If outdoor unit is No. 30)
PUMP DOWN(CN042)
EEPROM(IC006)
C1(CN021,BLK)
TO(CN022,WHT)
TD,TS(CN023,WHT)
SILENT MODE(CN028,WHT)
RC-P(CN034,RED)
FAN(CN030,WHT)
ROM(CN012,WHT)
OC(CN013,BLU)
EMG(CN014,BRN)
20S(CN09,WHT)
FUSE(30A,F003)
<Approximately 4 – 5 minutes are required.>
1-333
System address
System address
10s digit
No.
(2P DIP switch)
Both OFF
ON
(Setting at shipment = "0")
1
Both OFF
ON
1
Both OFF
ON
1
10s digit ON
ON
1
20s digit ON
ON
1
10s digit and 20s
digit ON
ON
1
System address
1s place
(Rotary switch)
"0" setting
ON
2
OFF
"1" setting
ON
2
OFF
"2" setting
ON
2
OFF
"1" setting
ON
2
OFF
"1" setting
ON
2
OFF
"0" setting
ON
2
OFF
1