Check Prior to Auto Address Setting
If an outdoor unit displays an alarm, conduct this process after diagnosing the problem.
1 Auto
Address
1-1
Is the power of the indoor unit(s) and outdoor unit(s) on?
2
Indoor/
Has the wiring of the indoor/outdoor control line been completed?
2-1
outdoor
Is it all connected?
control line
Has high voltage (over AC200V) been applied to the control line
2-2
circuit? Has the fuse on the control PC board blown?
(Check each board of the indoor unit(s) and outdoor unit(s).)
The power line and indoor/outdoor control line are miswired. Turn off the power, check &
2-3
correct the miswiring and then make connections of the indoor/outdoor control lines to the
emergency side of all the control PC boards and controllers.
3
Installation
Be sure that the indoor and outdoor units are connected
or setting
3-1
with correct combination written in catalog.
related
Is the indoor/outdoor control line connected to more than one
3-2
outdoor unit? (Network wired?)
Is the Terminal resistor select switch on the outdoor control PC board
3-3
set to just one unit?
3-4
Are other outdoor units using a duplicate setting?
When units are networked, first set the system address for each outdoor unit in the order
3-5
1-2-3 and then run auto address setting.
3-6
Run the auto address setting.
5-7
Yes
2-1
No
Power on
Yes
2-2
No
Connect the wiring
Yes
2-3
No
3-1
Yes
3-2
No
Correct the connection
Yes
3-3
No
3-6
Yes
3-4
No
Correct the setting
Yes
3-5
No 3-6
5