Panasonic S-45PU1E5 Technical Data & Service Manual page 380

Table of Contents

Advertisement

1
Refrigerant charging
For PE1 Type
For the twin connection, the amount of refrigerant required for pipe length 30m has been included in this unit
at the factory while that required for pipe length 20m has been included for the triple/double-twin connections.
No additional charge is required for the first 30m pipe length in the case of the twin connection and for the first
20m in the case of the triple/double-twin connections. The amount of included refrigerant for each model is
listed on NAME PLATE.
Make additional charges by adding up pipe length in an order of main pipe (L)
wide diameter) and then selecting the amount of refrigerant corresponding to the remaining (after 30m for the
twin connection and after 20m for the triple/double-twin connections) liquid side pipe diameter and pipe length
from the below table.
Liquid pipe diameter
ø6.35
ø9.52
For PEY1 Type
For the twin connection, the amount of refrigerant required for pipe length 30m has been included in this unit
at the factory. No additional charge is required for the first 30m pipe length in the case of the twin connection.
The amount of included refrigerant for each model is listed on NAME PLATE.
Make additional charges by adding up pipe length in an order of main pipe (L)
diameter) and then selecting the amount of refrigerant corresponding to the remaining (after 30m for the twin
connection) liquid side pipe diameter and pipe length from the below table.
Liquid pipe diameter
ø6.35
ø9.52
Wiring
For PE1 Type
Earth
L
N
Controll
cable
U1
U2
R1
R2
Indoor unit
(DOUBLE TWIN type)
For PEY1 Type
Earth
L
N
Controll
cable
U1
U2
R1
R2
Indoor unit
Addition amount of refrigerant [g/m]
Addition amount of refrigerant [g/m]
Earth
Earth
L
L
N
N
Controll
cable
U1
U1
U2
U2
R1
R1
R2
R2
Indoor unit
Indoor unit
(TRIPLE type)
Power supply
(220/230/240V~)
Circuit breaker
Circuit breaker
Switch
Earth
Controll
L
N
cable
U1
U2
R1
R2
Indoor unit
Outdoor unit
Wired remote
controller
(unit: mm)
20
50
(unit: mm)
20
50
Power supply
(220/230/240V~)
Circuit breaker
Switch
Earth
L
N
Controll
cable
U1
U2
R1
R2
Indoor unit
Wired remote
controller
SG : Shows the earth for the shielded cable.
Power supply
Power supply
(220/230/240V~)
(380/400/415V 3N~)
Circuit breaker
Switch
Switch
L
L1
N
L2
L3
N
Earth
Earth
Outdoor unit
U1
U2
SG : Shows the earth for the shielded cable.
1-370
branch pipe (La
branch pipe (La
Power supply
(220/230/240V~)
Circuit breaker
Circuit breaker
Switch
L
Controll
N
cable
Earth
U1
U2
Outdoor unit
Lb
Lc
Lb wide
Power supply
(380/400/415V 3N~)
Switch
L1
L2
L3
N
Earth
Outdoor unit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents