INSTALLER TESTS

Use the installer tests to check out the system:
• Equipment Test: Tests the heating, cooling, fan, and IAQ
equipment. The test allows you to manually call for each
system to ensure the equipment and thermostat operate
properly. Any minimum off timers are ignored during the
system test. You can test the following equipment:
— Heat
— Em Heat
— Cool
— Fan
— Humidification
— Dehumidification
— Ventilation
— Economizer
— Time of Day
• Wireless Test: Run this test to verify that the thermostat
can communicate properly in the installed location. The test
measures the signal strength between the
— Thermostat and the Equipment Interface Module (in
non-zoned applications)
— Thermostat and the TrueZONE Wireless Adapter (in
zoned applications)
Accessing Installer Tests
1. Press MENU on the home screen, then scroll down to
Installer Options and press SELECT.
2. Enter the password (date code) when prompted. See
"Finding Your Password (Date Code) to Access Installer
Options" beginning on page 19 for more information.
3. Scroll down to Installer Test and press SELECT.
4. Select Equipment Test or Wireless Test.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during
the Equipment Test
Avoid cycling compressor quickly.
Fig. 64.
Fig. 65.

Using the Equipment Test

1. Select the equipment you want to test and press the
arrow buttons to turn the equipment on/off. Press Back to
test the remaining equipment.
NOTE: The time out for the Equipment Test mode is 30
minutes (if there is no keypress for 30 minutes,
the thermostat will automatically exit the Equip-
ment Test).
2. Run Time, Discharge, Return and Delta T data are dis-
played for heating and cooling tests (requires Discharge
and Return Air Sensors). See Fig. 68.
The Discharge, Return and Delta T are updated every 30
seconds during the test. The Run Time counter starts
over when the next stage is turned on.
57
®
VISIONPRO
8000 WITH REDLINK™
Fig. 66.
Fig. 67.
Fig. 68.
68-0312—03