Honeywell TH8320R1003 Installation Manual page 42

Visionpro 8000 with redlink
Hide thumbs Also See for TH8320R1003:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
503
Indoor Sensor
10K
Type
20K
504
Use [T-Stat Sensor]
Use T-Stat Sensor for Temp Ctrl -
for Temp Ctrl
Yes or No
Use [Remote Indoor
Use [Remote Indoor Sensor
Sensor Name] for
Name] for Temp Ctrl - Yes or No
Temp Ctrl
Use T-Stat Sensor in Temp Avg -
Use [T-Stat Sensor]
Yes or No
in Temp Avg
Use [Remote Indoor Sensor
Use [Remote Indoor
Name] in Temp Avg - Yes or No
Sensor Name] in
(Up to 6 Remote Indoor Sensors)
Temp Avg
505
Outdoor Sensor
None
S1
S2
S3
S4
507
Return Sensor
None
S1
S2
S3
S4
508
Return Sensor
10K
Type
20K
509
Discharge Sensor
None
S1
S2
S3
S4
68-0312—03
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
10K:
if ISU 101
Application is
Residential
20K:
if ISU 101:
Application is
Commercial
Sensors are
Averaged (T-
Stat Sensor
and Remote)
None
None
10K
None
42
Residential,
Commercial
Requires
or Both
EIM
Both
No
Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
C7189U1005 = 10K ohm
C7772 = 20K ohm
TR21 = 20K ohm
TR21-A = 10K ohm (IMPORTANT - the TR21-
A must be used in combination with a TR21
sensor or another TR21-A sensor for the
thermostat to calculate the correct indoor
temperature reading).
See "Wiring guide — Wired Indoor Sensors"
beginning on page 135 for information on the
sensor type you should select based on how
the sensors are wired. For example, you
would select 20K when you have two TR21-A
(10K) sensors wired in series.
Both
No
Select the sensors to be used for temperature
control. If you select more than one, the
thermostat will average the temperature
readings from each sensor.
See "Remote Indoor Sensors" beginning on
page 112.
Both
No
Select the terminals wired to the Outdoor
Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and
S4
Both
Yes
Select the terminals wired to the Return
Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and
S4
Both
Yes
Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
Both
No
Select the terminals wired to the Discharge
Sensor.
Number of Sensor Inputs:
Thermostat = S1
Equipment Interface Module = S1, S2, S3 and
S4
Notes