Wiring guide — Wired Indoor Sensors
CAUTION
Electrical Interference (Noise) Hazard.
Can cause erratic system operation.
Keep wiring at least one foot away from large inductive
loads such as motors, line starters, lighting ballasts and
large power distribution panels.
Use shielded cable to reduce interference when
rerouting is not possible.
IMPORTANT
Erratic temperature readings from a sensor can occur
as a result of any of the wiring practices described
below. Avoid these practices to assure correct opera-
tion. Use shielded cable to reduce interference if
rerouting sensor wiring is not possible.
— Be sure wires have a cable separate from the thermo-
stat cable.
— Do not route temperature sensor wiring with building
power wiring, next to control contactors or near light
dimming circuits, electric motors or welding
equipment.
— Avoid poor wiring connections.
— Avoid intermittent or missing building earth ground.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Use the S1, S2, S3 or S4 terminals for wired sensors.
Wiring 4 C7189U1005 sensors (10k ohm) for temperature
averaging network. Select 10K in the Installer Setup (ISU 503)
when using C7189U1005 sensor(s).
EIM
THE NUMBER OF C7189U SENSORS MUST BE
1
A SQUARE NUMBER (1, 4, 9, 16, ETC.)
Fig. 343. Wiring 4 C7189U sensors.
1
C7189
C7189
C7189
C7189
M31472
Wiring 2 TR21 sensors (20k ohm) and 1 TR21-A sensor (10k
ohm) for temperature averaging network. Select 20K in the
Installer Setup (ISU 503) when using 2 TR21 sensors and 1
TR21-A sensor.
EIM
Fig. 344. Wiring 2 TR21 sensors and 1 TR21-A sensor.
Wiring 4 TR21 sensors (20k ohm). Select 20K in the Installer
Setup (ISU 503) when using TR21 sensor(s).
EIM
Fig. 345. Wiring 4 TR21 sensors.
Wiring 2 TR21-A sensors (10k ohm) for temperature averaging
network. Select 20K in the Installer Setup (ISU 503) when
using 2 TR21-A sensors in series. Note: The TR21-A sensor
must be used in combination with TR21 or TR21-A sensor.
EIM
Fig. 346. Wiring 2 TR21-A sensors.
135
®
VISIONPRO
8000 WITH REDLINK™
TR21-A
T3
T4
TR21
TR21
M31473
TR21
TR21
TR21
TR21
M31474
TR21-A
T3
T4
TR21-A
T3
T4
M31475
68-0312—03