Honeywell TH8320R1003 Installation Manual page 122

Visionpro 8000 with redlink
Hide thumbs Also See for TH8320R1003:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™
Typical wiring for geothermal radiant heat, geothermal forced-air, and backup heat with one transformer.
4
1 U1, U2 or U3 terminals must be used for geothermal radiant heat (ISU 201). Thermostat allows 2 stages of radiant heat—geo-
thermal (stage 1) and boiler (stage 2).
2 "U" terminals are normally open dry contacts when set up for geothermal radiant heat. You must install a field jumper if radiant
heat is powered by system transformer. Do NOT install a field jumper if radiant heat has its own transformer.
3 L/A terminal sends continuous output when thermostat is set to EM HEAT mode except when set up for Economizer or TOD. See
"Economizer Module Wiring Diagrams" beginning on page 132.
4 Wire a maximum of 4 sensors using the S1-S4 terminals. S1-S4 terminals can be connected to an indoor sensor, outdoor sensor,
discharge sensor, return sensor, dry contact device to display an alert or an occupancy sensor for remote setback.
5 Connect wireless adapter to ABCD for extended wireless range.
NOTE: For setup and operation, see "Geothermal Radiant Heat" beginning on page 78.
68-0312—03
EIM
POWER
HEAT
COOL
STATUS
FAN
LEDS
U1
U2
U3
OPTIONAL
JUMPER
2
A
B
C
5
D
S4
CONNECT OPTIONAL
S4
SENSORS TO
S3 AND S4 TERMINALS
S3
S3
Fig. 316. EIM wiring guide — geothermal radiant heat.
TO THERMOSTAT
HEAT PUMP
O/B
AUX1
AUX1
AUX2
AUX2
L/A
3
JUMPERS
SENSORS
122
O/B
CHANGEOVER VALVE
BACKUP HEAT
STAGE 1
BACKUP HEAT
STAGE 2
COMPRESSOR
Y
STAGE 1
COMPRESSOR
Y2
STAGE 2
G
FAN RELAY
L
COMPRESSOR MONITOR
OR ZONE PANEL
3
GEOTHERMAL RADIANT
HEAT STAGE 1
1
AIR HANDLER
TRANSFORMER
R
24
120
C
VAC
VAC
2
CONNECT OPTIONAL
SENSORS TO
S1 AND S2 TERMINALS
4