ISU
Installer Setup
Number
Name
510
Discharge Sensor
10K
Type
20K
511
A-Coil Low Temp.
Off
Cutoff
35° F to 65° F (in 5° F increments)
600
Dry Contact
No
Device on S
Yes
Terminals
600
Remote Setback
No
Dry Contact
Yes
600
Full Drain Pan Dry
No
Contact Alert
Yes
600
Dirty Filter Dry
No
Contact Alert
Yes
600
Water Leak Dry
No
Contact Alert
Yes
600
Sys. Shutdown
No
Dry Contact Alert
Yes
600
Service Needed
No
Dry Contact Alert
Yes
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
10K
Off
No
No
No
No
No
No
No
43
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
Select 10K or 20K based on the sensor
installed. Refer to resistance values below:
50062329-001 = 10K ohm
32005180-002 = 10K ohm
C7735A1000 = 10K ohm
C7770A = 20K ohm
C7041 = 20K ohm
Both
No
If an optional Discharge Sensor is used, this
feature can help prevent icing on the air
conditioning A-Coil.
When temperature reaches the limit you set,
compressor(s) will shutoff while the system
fan continues to run, until the temperature
rises to a safe level.
Both
Yes
Dry Contact Alerts and Remote Setback
require an Equipment Interface Module. This
ISU is only displayed if an S1-S4 terminal is
available.
See "Dry Contact Alerts" beginning on
page 74 and "Remote Setback (Commercial
Use)" beginning on page 105.
Commercial
Yes
Remote Setback requires an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See "Dry Contact Alerts" beginning on
page 74.
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See "Dry Contact Alerts" beginning on
page 74.
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See "Dry Contact Alerts" beginning on
page 74.
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See "Dry Contact Alerts" beginning on
page 74.
Both
Yes
Dry Contact Alerts require an Equipment
Interface Module. This ISU is only displayed if
an S1-S4 terminal is available.
See "Dry Contact Alerts" beginning on
page 74.
®
8000 WITH REDLINK™
Notes
68-0312—03