Honeywell TH8320R1003 Installation Manual page 33

Visionpro 8000 with redlink
Hide thumbs Also See for TH8320R1003:
Table of Contents

Advertisement

ISU
Installer Setup
Number
Name
315
Heat Cycles Per
1 to 12 CPH
Hour Stage 2
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type.
315
Heat Cycles Per
1 to 12 CPH
Hour Stage 3
Note: Depending
on the application,
the text displayed
on the screen may
show the specific
heating equipment
type.
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Conv. Forced
Air = 5 CPH
Heat Pump =
3 CPH
Radiant Heat =
3 CPH
Conv. Forced
Air = 5 CPH
Heat Pump =
3 CPH
Radiant Heat =
3 CPH
33
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Both
No
This ISU is only displayed when ISU 207 Heat
Stages is set to 2 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load. The
recommended cycle rate settings are below
for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
Both
No
This ISU is only displayed when ISU 207 Heat
Stages is set to 3 stages.
Cycle rate limits the maximum number of
times the system can cycle in a 1 hour period
measured at a 50% load. For example, when
set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10
minutes on, 10 minutes off). The system
cycles less often when load conditions are
less than or greater than a 50% load. The
recommended cycle rate settings are below
for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH
High Efficiency Gas Forced Air = 3 CPH
Oil Forced Air = 5 CPH
Electric Forced Air = 9 CPH
Hot Water Fan Coil = 3 CPH
Hot Water Radiant Heat = 3 CPH
Geothermal Radiant Heat = 3 CPH
Steam = 1 CPH
Gravity = 1 CPH
®
8000 WITH REDLINK™
Notes
68-0312—03