TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS (TABLE 4)

Configure Installer Setup

1. Press and release the System key.
2. Press System and Done keys simultaneously.
3. Hold keys for approximately five seconds, until the
screen changes.
4. When the display changes, release the System and
Done keys.
NOTE: See Table 4 for installer setup (ISU) numbers
and settings.

Installer System Tests

Use the Installer System Test section to test the heating,
cooling and fan. Refer to the latter portion of Table 4.
Installer
Setup
Installer Setup
Number
Name
0120
Date (Year Upper)
0130
Date (Year Lower)
0140
Date (Month)
0150
Date (Day)
0160
Schedule Options
0170
System Selection
0175
TOD/Economizer
output (terminal A)
0180
Heat Fan Operation 0
0185
Pre-occupancy
Purge Duration
0190
Reversing Valve
O/B
0220
Cycles Per Hour
(CPH) for first stage
compressor
0230
CPH for second
stage compressor
62-0221—05
Table 4. Installer Setup Menu.
Default
Setting
All Settings
20
20—20xx
21—21xx
04
00-99
6
1-12
15
1-31 (Month Dependent)
4
0—Non-Programmable
4—Programmable
8
1—1H/1C Conv
2—1H/1C HP
3—1H w/o fan
4—1H with fan
6—1C
7—2H/1C HP (Aux. Heat)
8—2H/2C Conv
9—2H/1C Conv
10—1H/2C Conv
11—2H/2C HP
12—3H/2C HP (Aux.
Heat)
0
0—Unused
1—TOD
2—Economizer
0—System controls fan
1—Thermostat controls
fan (ON during call for
heat)
0
0—no duration
1—one hour
2—two hours
3—three hours
0
0—O (O/B On Cool)
1—B (O/B On Heat)
3
1-6
3
1-6
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed
during Installer System Test
Avoid cycling compressor quickly.
IMPORTANT
Use Installer System Test to test heating, cooling
and fan. The setting chosen for System Type
(Installer Setup Number 0170) can prevent some
System Test Numbers from appearing.
Available year range: 2001 - 2178
Available year range: 2001 - 2178
To use the Emergency Heat button, select setting
#7 or #12. See Fig. 16 or 17 for auxiliary heat
wiring.
Economizer energizes A during a call for cool.
TOD energizes A during Occupied period, and de-
energizes A during Unoccupied.
Only shown for conventional system with heat
stages (ISU 0170) and fan capability selected.
If heat pump is selected, fan always operates with
Thermostat control.
The only thing that allows the fan to turn off during
occupied periods is a manual override of the fan
from On to Auto.
Only shown if thermostat is programmable (ISU
0160).
Pre-occupancy purge enabled by nonzero duration
(and sends economizer to minimum position).
Only shown with heat pump system selected.
Only shown for system with cool stages (ISU
0170). Selection in this stage changes second
stage cool default CPH.
Only shown for system with two stages of cool
(ISU 0170).
10
Notes

Advertisement

Table of Contents
loading

Table of Contents