VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
409
Adaptive Recovery
No
Yes
410
Minimum Cool
50° F to 99° F
Setpoint
410
Maximum Heat
40° F to 90° F
Setpoint
411
Keypad Lockout
Unlocked
Partially Locked
Fully Locked
412
Residential:
None
Entry / Exit
50° F to 99° F
Remote - Home
Cool Setpoint
Note: setpoint is limited based on
setting at ISU 410.
Commercial:
Entry / Exit
Remote -
Occupied Cool
Setpoint
412
Residential:
None
Entry / Exit
40° F to 90° F
Remote - Home
Heat Setpoint
Note: setpoint is limited based on
setting at ISU 410.
Commercial:
Entry / Exit
Remote -
Occupied Heat
Setpoint
413
Residential:
None
Entry / Exit
50° F to 99° F
Remote - Away
Cool Setpoint
Note: setpoint is limited based on
setting at ISU 410.
Commercial:
Entry / Exit
Remote -
Unoccupied Cool
Setpoint
68-0312—03
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Yes
50° F
90° F
Unlocked
75° F
70° F
78° F
40
Residential,
Commercial
Requires
or Both
EIM
Residential
No
No: The system will begin heating or cooling
recovery at the scheduled time.
Yes: The thermostat will begin heating or
cooling recovery early to ensure that the
temperature is reached at the scheduled time.
The thermostat will adjust the start time of the
equipment based on how quickly the
scheduled temperature was reached on
previous days. See page 71 for more
information on Adaptive Intelligent Recovery.
Both
No
The user cannot set the temperature below
this level.
Both
No
The user cannot set the temperature above
this level.
Both
No
Unlocked: User has access to all thermostat
settings.
Partially Locked: User can modify only
temperature settings.
Fully Locked: User cannot modify any
settings.
Both
No
The thermostat maintains this Cool setting
when the user presses Home / Occupied at the
Entry / Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
"Wireless Entry/Exit Remote" beginning on
page 110.
Both
No
The thermostat maintains this Heat setting
when the user presses Home / Occupied at the
Entry / Exit Remote. Select None to delete this
temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
"Wireless Entry/Exit Remote" beginning on
page 110.
Both
No
The thermostat maintains this Cool setting
when the user presses Away / Unoccupied at
the Entry / Exit Remote. Select None to delete
this temperature setting. The thermostat only
responds to the Entry / Exit Remote if a
temperature is pre-set at this screen. See
"Wireless Entry/Exit Remote" beginning on
page 110.