VISIONPRO
8000 WITH REDLINK™
ISU
Installer Setup
Number
Name
1012
Vent Priority
Lockouts
ASHRAE
1013
Low Outdoor
Off
Temp Vent
-20° F to 40° F (in 5° F
Lockout
increments)
1013
High Outdoor
Off
Temp Vent
80° F to 110° F (in 5° F
Lockout
increments)
1013
High Out. Dew
Off
Point Vent
65° F to 85° F (in 5° F increments)
Lockout
68-0312—03
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
Lockouts
Off
Off
Off
54
Residential,
Commercial
Requires
or Both
EIM
Residential
No
Lockouts are Priority: The thermostat places
a priority on lockouts versus the ASHRAE 62.2
ventilation standard. The thermostat will not
run ventilation during the following lockout
conditions (if configured) unless you
manually call for ventilation:
Lockout Ventilation during Outdoor Conditions
(ISU 1013)
Lockout Ventilation on Humidification or
Dehumidification Calls (ISU 1014)
Lockout Ventilation during "Sleep" (Residential)
or "Unoccupied" (Commercial) program
periods. Note: This option is set by the user on
the Ventilation screen in the Menu.
ASHRAE is Priority: ASHRAE requires
additional ventilation following a long off
cycle. The thermostat meets the ASHRAE 62.2
ventilation standard by running additional
ventilation when outdoor conditions are
favorable. If ASHRAE cannot be met when
outdoor conditions are favorable, the
thermostat will override the outdoor lockouts
and run ventilation. When using this option, it
is recommended to increase the rate (CFM) of
the ventilation equipment to meet the ASHRAE
62.2 ventilation standard in a shorter run time.
Notes:
ISU 1014 Lockout Ventilation on Humidification
or Dehumidification calls is not an option when
you select ASHRAE is Priority.
The ability to lockout ventilation during the
"Sleep" or Unoccupied program periods is not
an option when you select ASHRAE is Priority.
Both
No
Requires an outdoor sensor.
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See "Ventilation — Outdoor Condition
Lockouts (ISU 1013)" beginning on page 91.
Both
No
Requires an outdoor sensor.
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See "Ventilation — Outdoor Condition
Lockouts (ISU 1013)" beginning on page 91.
Both
No
Requires a Wireless Outdoor Sensor (sense
outdoor humidity).
This ISU is only displayed when ISU 1000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See "Ventilation — Outdoor Condition
Lockouts (ISU 1013)" beginning on page 91.
Notes