ISU
Installer Setup
Number
Name
907
Dehum Over
0°, 1°, 2°, 3° F
Cooling Limit
908
DehumControl
Basic
Minimum On Time
Cooling Droop
Reheat
909
Dehum Minimum
5 to 15 minutes
On Time
910
Dehum Over
1° F to 5° F
Cooling Limit
912
User Dehumidifier
User Dehumidifier in Heat Mode -
No or Yes
in Heat Mode
Use Dehumidifier in Cool Mode -
Use Dehumidifier
No or Yes
in Cool Mode
Use Dehumidifier in Off Mode - No
Use Dehumidifier
or Yes
in Off Mode
Table 2. Installer Setup (ISU) Table. (Continued)
Settings
Default
3° F
Basic
10 minutes
2° F
Use
Dehumidifier in
Cool Mode -
Yes
Default varies
based on
heating/cooling
equipment
selected
51
VISIONPRO
Residential,
Commercial
Requires
or Both
EIM
Residential
No
This ISU is only displayed when ISU 900
Dehum Equipment is set to A/C with Low Fan
or A/C with High Fan.
The thermostat uses the cooling system to
reduce humidity by lowering the temperature
up to 3° F below the current cool setpoint until
the desired humidity level is reached.
The thermostat keeps the temperature below
the cooling setpoint until the desired humidity
level is reached.
0° F is only an option when ISU 900 Dehum
Equipment is set to A/C with Low Fan.
Commercial
No
See "Dehumidification - Commercial"
beginning on page 87.
Commercial
No
This ISU is only displayed if ISU 908 Dehum
Control is set to Minimum On Time. This
option ensures that the compressor runs long
enough to effectively reduce humidity when
the cooling equipment is cycled on. The
compressor will run for the "minimum on
time" you set until the desired humidity level
is reached.
Commercial
No
This ISU is only displayed if ISU 908 Dehum
Control is set to Cooling Droop. The
thermostat uses the cooling system to reduce
humidity by lowering the temperature up to 5°
F below the current cool setpoint until the
desired humidity level is reached.
The thermostat keeps the temperature below
the cooling setpoint until the desired humidity
level is reached.
Both
No
This ISU is only displayed when ISU 900
Dehum Equipment is set to Dehumidifier.
Heat: Includes Heat, Emergency Heat and
Auto. If the system is in Auto mode, the
thermostat will allow dehumidification if the
last call was for heat.
Cool: Includes Cool and Auto. If the system is
in Auto mode, the thermostat will allow
dehumidification if the last call was for cool.
Off: The thermostat will allow
dehumidification when the system setting is
Off.
See "Dehumidification - Residential"
beginning on page 83 or "Dehumidification -
Commercial" beginning on page 87.
®
8000 WITH REDLINK™