Output Signal (Do) Forced Output - Mitsubishi Electric MELSERVO MR-J2S- A Instruction Manual

General-purpose ac servo general-purpose interface servo amplifier
Table of Contents

Advertisement

6. DISPLAY AND OPERATION

6.7 Output signal (DO) forced output

The output signal can be forced on/off independently of the servo status. This function is used for output
signal wiring check, etc. This operation must be performed in the servo off state servo-on (SON).
Operation
Call the display screen shown after power-on.
Using the "MODE" button, show the diagnostic screen.
CN1A
14
POINT
When the servo system is used in a vertical lift application, turning on the
electromagnetic brake interlock (MBR) after assigning it to pin CN1B-19
will release the electromagnetic brake, causing a drop. Take drop
preventive measures on the machine side.
CN1B
CN1B
CN1B
CN1B
CN1A
CN1A
18
4
6
19
18
19
Press UP twice.
Press SET for more than 2 seconds.
Switch on/off the signal below the lit segment.
Always lit
Indicates the ON/OFF of the output signal. The correspondences
between segments and signals are as in the output signals of the
external I/O signal display.
(Lit: ON, extinguished: OFF)
Press MODE once.
The segment above CN1A-pin 18 is lit.
Press UP once.
CN1A-pin 18 is switched on.
(CN1A-pin 18-SG conduct.)
Press DOWN once.
CN1A-pin 18 is switched off.
Press SET for more than 2 seconds.
6 - 12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melservo-j2-super seriesMr-j2s-*aMr-j2s- a seriesMr-j2s-20a

Table of Contents