Event Codes; Ademco Contact Id & Sia Formats - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Programming
CENTRAL STATION

1=EVENT CODES

Primary/Secondary Screen #4
Event Description
PULL STATION
MON-USER-DEF-1
WATERFLOW
MON-USER-DEF-2
SMOKE (PHOTO)
DET-USER-DEF-1
SMOKE (ION)
DET-USER-DEF-2
HEAT DETECT
DET-USER-DEF-3
SMOKE DUCT-P
DET-USER-DEF-4
122
The Communication Format is determined by the type of receiver that the DACT is transmitting to.
Consult your Central Station for proper selection or consult our factory representatives. For any
format chosen, the control panel automatically programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while viewing the
Comm Format screen. The following table describes each format:
Screen Selection
ADEMCO CONTACT ID
SIA 8
SIA 20
Event Codes
Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following screen to be
displayed:
Pressing the down arrow key allows viewing of all Events associated with the selected
Communication Format. Pressing the number corresponding to the event displayed in each screen
will display its default event code which can be customized by the programmer. For example,
pressing 1 for Pull Station will display the following screen which allows the Event Code to be
changed from the default value.
The tables on the following pages list all of the Events and their default Event Codes for the various
Communication Formats.
Ademco Contact ID & SIA Formats
The information shown in Table 3.11 is automatically programmed for the Central Station phone
number Event Codes when the Ademco Contact ID or SIA Format is selected. Enter 0s for an
Event Code Setting to disable the report. Disabled reports will not get called to the Central Station.
The programmer may enable the Event Types in programming as described on the previous page.
Active
115
115
113
113
111
111
111
111
114
114
116
116
Table 3.11 Event Codes
Communication Format Description
Contact ID, DTMF, 1400/2300 ACK
Security Industry Association, 8 messages per call
Security Industry Association, 20 messages per call
Table 3.10 Communication Formats
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1
3=WATERFLOW
Event Code Screen
PULL STATION
ALARM
Event Code Screen
Ademco Contact ID
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
Zone
Point
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Master Programming Level
000
SIA
Active
FA
FA
SA
SA
FA
FA
FA
FA
KA
KA
FA
FA
Restoral
FH
FH
SH
SH
FH
FH
FH
FH
KH
KH
FH
FH