4: Trouble Reminder; 5: Timers; 6: Nac; 7: Relays - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Read Status
4.23.4 Trouble Reminder
READ STATUS
Pressing 1 while viewing Read Status Screen #2 will display the following screen:
1=TROUBLE REMINDER
2=TIMERS
3=NAC
Read Status Screen #2
The screen indicates whether the Trouble Reminder feature is On or Off.
4.23.5 Timers
Pressing 2 while viewing Read Status Screen #2 will cause the following Timer screens to be
displayed:
These screens will indicate the delay time, in seconds, for each of the first three possible delay
options. The AC Loss Delay time is displayed in hours.
4.23.6 NAC
Each NAC can be programmed individually with unique settings with the exception of Canadian
Mode. When the Canadian Option is seletected in programming (see "Canadian Option" on
page 100), all NAC settings are changed to that of NAC 1. While in Canadian Mode, if any NAC is
setting is changed, all other NACs will get those same settings. Pressing 3 while viewing Read
Status Screen #2 will display the following screen:
The operator can press 1 to view the programmed options for NAC 1, 2 to view the programmed
options for NAC 2, 3 to view the programmed options for NAC 3, or 4 to view the programmed
options for NAC 4. The resulting screens will display the following information:
4.23.7 Relays
READ STATUS
Pressing 1 while viewing Read Status Screen #3 will display the following screen:
1=RELAYS
2=PROGRAM CHECK
3=HISTORY
Read Status Screen #3
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
TIMERS
PAS DELAY
PRE SIGNAL
WATERFLOW
Enable/Disable Status
Circuit Type (Bell, Strobe, etc.)
Silenceable/Nonsilenceable
Auto Silence Enable/Disable and time delay (in minutes)
Coding Selection (Temporal, Steady, etc.)
Zone Assignments
Silence Inhibit Enabled/Disabled
Synchronization Type (System Sensor, Wheelock, or Gentex)
MNS Override Enabled/Disabled
TROUBLE REMINDER
TROUBLE REM
ON
000
AC LOSS DELAY
000
000
NAC
1=NAC 1
3=NAC 3
2=NAC 2
4=NAC 4
RELAY
1=RELAY 1
2=RELAY 2
3=RELAY 3