Installation
Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
ANN-80 Remote Fire Annunciator
Specifications
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no activity): 37.0 mA
Trouble: 39.0 mA
Alarm: 40.0 mA
AC Fail ( not backlit): 15.0 mA
For use indoors in a dry location
Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the annunci-
ator.
Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the termi-
nal block and DIP switches (refer to figure below):
1.
Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise.
2.
Push in the snap latch located on the right side of the unit while pulling the cover open.
3.
To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the
cover closed, snapping it shut.
46
Address
Switch 5
not valid
OFF
OFF
01
OFF
OFF
02
OFF
OFF
03
OFF
OFF
04
OFF
OFF
05
OFF
OFF
06
OFF
OFF
07
OFF
OFF
08
OFF
ON
Switch 4
Switch 3
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
OFF
OFF
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Optional Module Installation
Switch 2
Switch 1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF