Master Programming Level

Pre-signal

EDIT MONITOR
1=PRE-SIGNAL
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display
reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal
Edit Monitor Screen #3
Yes and Pre-signal No. Refer to"Presignal" on page 141 for additional information.

Walktest

EDIT MONITOR
The Walktest feature allows one person to test the system devices without the necessity of manually
1=WALKTEST

2=ZONE ASSIGNMENT

resetting the control panel after each device activation. To enable devices, which are connected to
00    
a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until
Edit Monitor Screen #4
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between
Walktest Yes and Walktest No. Refer to "Walktest" on page 144 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2
while viewing Edit Monitor Screen #4 displays the following screen:
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zones Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Monitor Screen #4.

Noun/Adjective

EDIT MONITOR
1=NOUN/ADJECTIVE
The Noun/Adjective selection allows the programmer to enter specific descriptors about the
2=DESCRIPTION

monitor module currently being programmed. Pressing 1 while viewing Edit Monitor Screen #5
Edit Monitor Screen #5
will cause the following screen to be displayed:
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
MON ZONE ASSIGN
Z00 Z Z Z Z
Zone Assignment Screen
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen
Programming