Section 3: Programming; Programming Data Entry - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific
values or not used at all as indicated below:
Program feature or
Permitted in
option
UL 864? (Y/N)
Trouble Call Limit
N
Remote Download
Y

3.1 Programming Data Entry

Programming can be accomplished using the MS-9200UDLS keypad or by connecting an optional
standard computer keyboard. The keyboard can be connected to the PS-2 connector J3 on the
control panel main circuit board.
The information presented in this section refers to programming the MS-9200UDLS via the
onboard keypad. If an optional computer keyboard is connected to the MS-9200UDLS main circuit
board, the following table describes the keyboard keys which correspond to the onboard keypad
keys.
63

Section 3: Programming

AND OTHER INVOLVED PARTIES
Possible settings
Refer to "Trouble Call Limit (Dialer Runaway Prevention)" on
page 120.
Trouble Call Limit = 0 (factory default): unlimited calling to
Central Station for any trouble condition
Trouble Call Limit = 1 - 99: limits call for each unique trouble
to from 1 to 99 within a 24 hour period
Refer to "Remote Site Upload/Download" on page 156.
Remote Download - Proprietary No
Remote Download - Proprietary Yes
Keypad Keys
1st Event
CLR
ESC
RECALL
*
#
A - Z
0 - 9
(on QZ key)
/
ENTER
ACK/STEP
SILENCE
DRILL
RESET
Computer Keyboard Keys
Home
Delete
Esc
Insert
*
#
A - Z
0 - 9
Space bar
/
Enter
F1
F2
F3
F4
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Settings permitted in UL
864
Trouble Call Limit = 0 for
unlimited Central Station
trouble calls
Remote Download
Proprietary Yes for
Proprietary system intended
to protect only contiguous
properties