Installation; Printer Configuration - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Installation

A parallel printer may also be connected to the FACP using the optional ANN-S/PG Serial/Parallel
Interface Module. Refer to "ANN-S/PG Serial/Parallel Interface Module" on page 23 for installa-
tion details. Refer to "ANN-BUS Options" on page 107 for programming information.
CAUTION:
!
DO NOT CONNECT A PRINTER OR PC TO THE MS-9200UDLS FACP IF A GROUND FAULT
(ZERO IMPEDANCE TO GROUND) EXISTS ON THE CONTROL PANEL. CIRCUIT DAMAGE
MAY RESULT. REMOVE ALL POWER (PRIMARY AND SECONDARY) BEFORE INSTALLING OR
REMOVING ANY WIRING.
Installation
Serial printers and PCs require separate primary power. Also required is the serial
PRT/PK-CABLE which is an interface cable prewired to a DB9F connector. Wire the PRT/PK-
CABLE to TB8 Terminals 1 - 4 as illustrated in the following figure. Connect the DB9F connector
to the printer or PC serial EIA-232 port. If a nine-pin serial connector is not available on the printer
or PC, use a DB25 adapter. Make certain that the DB25 adapter does not swap the Transmit and
Receive lines. Apply power to the FACP and printer or PC. Note that a ground fault (zero imped-
ance to ground) may occur on the FACP, dependent on the printer or PC being used, due to this
connection. For this reason, it is important that there be no preexisting ground fault on the panel.
Note that the printer may or may not be supervised as determined by user programming. Refer
to"Printer/PC" on page 125.

Printer Configuration

Refer to the documentation supplied with the printer for pertinent information about printer setup.
Set the printer's options as listed in the following table:
60
POSSIBLE EQUIPMENT DAMAGE
5 4 3 2 1
9 8 7 6
DB9F
Red
White
Green
Black
T
R
D
G
X
C
T
N
V
R
D
TB8
IN+ IN- OUT+ OUT-
Figure 2.33 Serial Printer and Computer Connections
COMMUNICATION SETUP
BUFFER:
DATA BITS:
PARITY:
STOP BIT:
BAUD RATE:
AUTOMATIC LINE FEED
AUTOMATIC CARRIAGE RETURN
Table 2.3 Printer Options
PRT/PK-CABLE
SLC
SLC
SLC
SHIELD
TB9
TB10
SLC
B+ A+ B- A-
A
B
ACS
LARGE
7
EVEN
1 STOP
2400/4800/9600
NO
NO
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014