MBT-1 Municipal Box Trip - Silenceable
C.2 MBT-1 Municipal Box Trip - Silenceable
The following figure illustrates the connection of the MBT-1 (Municipal Box Trip) between the
FACP and a Local Energy Municipal Box. The use of an addressable control module programmed
for General Alarm and Silenceable allows silencing of the Municipal Box without resetting the
panel or box.
The addressable Control Module must be programmed
as Silenceable and General Alarm.
-
+
+
TB2
TB1
JP7
+ -
+ 24V -
REMOTE PWR
NON-RST
SUPPLY SYNC
POWER
*If the SLC device does not match the one in this figure, refer to the SLC manual wiring conversion
charts for legacy and newer versions of the modules.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
T11
T10
T1
T9
T2
T8
T3
T7
T4
T6
T5
CMF-300
Control Module*
Alarm polarity shown!
-
24 VDC, Nonresettable
TB3
TB4
TB7
+ 24V -
NO NC C
1B+ 3B+ 3B- 1B-
2B+ 4B+ 4B- 2B-
RST
POWER
FACP Main Circuit Board
Figure C.5 MBT-1 Silenceable
NFPA Standard-Specific Requirements
Connect wires to two
red terminals on box.
Note: 10
maximum loop
resistance due to wiring from
power supply to Municipal Box.
(All contacts shown in energized position).
- To next device
+ on SLC Loop
Braided-shield/Drain Wire
EOLR-1 Power
Supervision Relay
SLC Loop
TB5
TB6
TB8
NO NC C
NC NO C
Xmt Rcv Dtr Gnd
A
B
In+ In- Out+ Out-
FIRE
Gamewell Model M34-56
Local Energy Municipal Box
white wire
MBT-1
brown wire
red
+
-
B
B
Shield
TB9
TB10
+
-
B+ A+ B- A- A B
A
B
Slc Slc Slc Slc Shield
black
175