Central Station Primary And Secondary Phone Numbers; Test Time Interval - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Programming
CENTRAL STATION
1=PRIMARY
2=SECONDARY
3=REPORT STYLE
Central Station Screen #2
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
120
Trouble Call Limit (Dialer Runaway Prevention)
The Call Limit option limits the number of DACT trouble calls to the Central Station, to a
programmed amount between 0 and 99, for each unique trouble within a 24 hour period. Separate
limit counters keep track of each unique type of trouble. Note that the number of phone line
(communication) faults called to the Central Station are not limited by this feature. No subsequent
restoral message is sent to the Central Station(s) for a particular trouble whose call limit has been
reached. Local DACT annunciation will still track the particular trouble and restoral.
To set the Trouble Call Limit, press 3 while viewing Central Station Screen #1. The following
screen will be displayed.
Enter a value between 00 and 99, then press Enter to set the Call Limit to this value.
NOTE: Entering a value of 00 will disable the Trouble Call Limit allowing the DACT to call the
Central Station an unlimited number of times.

Central Station Primary and Secondary Phone Numbers

Pressing 1 for Primary or 2 for Secondary will display the following screens.
Note that the following information must be entered for both the Primary and Secondary Central
Station Phone Numbers.
CENTRAL STATION #
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
CENTRAL STATION
1=COMM FORMAT
ADEMCO-CONTACT-ID
Primary/Secondary Screen #3

Test Time Interval

Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be
displayed:
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
Test Time Interval Screen #1
The test report sent to the Central Station phone number may be sent once every 6, 8, 12, or 24
hours. Select the desired Test Time Interval by pressing the corresponding digit in the screens
shown above.
TROUBLE CALL LIMIT
00-99 RANGE
Trouble Call Limit Screen
CENTRAL STATION
24
1=PHONE NUMBER
0000
0021
Primary/Secondary Screen #2
CENTRAL STATION
1=EVENT CODES
Primary/Secondary Screen #4
TEST TIME INTERVAL
1=6 HOURS
Test Time Interval Screen #2
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014