Enable/Disable Module - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Programming
The programmer can change a module's existing or factory default programming by pressing 3 in
MODULES
the Modules Screen. The following screen will be displayed:
1=ADD
2=DELETE
3=EDIT
Modules Screen
A flashing cursor will appear in the position of the first asterisk to the left.
The programmer keys in the three digit module address, such as 002. When the last digit is keyed-
in, if the selected address corresponds to a control module, a screen displaying information about
the control module with the selected address will be displayed as illustrated in the following:
In the preceding example:
To change the programming for the displayed module, press the keyboard down arrow key to view
the following Edit Control screens:

Enable/Disable Module

EDIT CONTROL
1=ENABLED
2=TYPE
To Enable or Disable the control module, press the 1 key while viewing the Edit Control Screen #2.
3=SILENCEABLE
Each press of the key will toggle the screen between Enabled Yes and Enabled No. If Enabled No
Edit Control Screen #2
is selected, the module will not be polled by the control panel, preventing the module from
activating its output devices. The control panel will indicate a system trouble condition and the
Disable LED will turn on if any devices are disabled.
82
Edit Module Screen for Control Modules
Normal - indicates that the module with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device
Control - indicates that the selected module is a control module
S or * - represents Silenceable (S) or Nonsilenceable (*)
W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * =
Waterflow Timer Delay disabled)
ZNNN - represents the first of five possible software zones that the module is assigned to
(NNN = the three digit zone number from 000 - 099)
1M002 - represents the Loop, Device type and Device address (1 = SLC Loop, M=Module
and 002 = Module Address 02)
EDIT CONTROL
1=ENABLED
2=TYPE
CONTROL
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION

Edit Control Screen #4
EDIT MODULE
ENTER MODULE ADDRESS

Edit Module Screen
NORMAL
CONTROL
<ADJ><NOUN>
ZNNN
SW
1M002
Edit Control Screen #1
EDIT CONTROL
1=WALKTEST
YES
2=ZONE ASSIGNMENT
YES
EDIT CONTROL
1=MNS OVERRIDE
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Master Programming Level
YES
00    
Edit Control Screen #3
NO
Edit Control Screen #5