Components
Cabinet
The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour). Ample
knockouts are provided for system wiring. Also available is an optional dress panel (DP-9692),
which mounts to the inside of the cabinet (required by ULC for Canadian installations).
Optional
XRM-24B(E)
Standard
XRM-24B(E)
letter or number. This circuit board can also be identified by using the software revision of
#9200UDV4.0 (meaning version 4.0) or later.
Batteries
The MS-9200UDLS cabinet provides space for two bat-
teries (up to 18 Amp Hour). Batteries larger than 18
Amp Hour require an external charger such as the CHG-
75 or CHG-120F and a UL listed battery box such as the
BB-26 or BB-55F. Batteries must be ordered separately.
1.5.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC Signaling
Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wir-
ing and operation). This allows the control panel to continually process the information to deter-
mine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to
an SLC address that is set in the detector head using built-in rotary decimal switches. The maxi-
mum address cannot exceed address 99. Note that a blinking LED on an intelligent detector indi-
cates communication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or
LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series
devices. If a mix of old and new series devices are installed on the same loop, the FACP must be
programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible
addressable detectors.
1.5.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface between the con-
trol panel and conventional notification and initiating devices. Each module can be set to respond
to an address with built-in rotary switches. The maximum address cannot exceed address 99. Note
that a blinking LED on an addressable module indicates communication between the module and
the control panel.
These devices (i.e., MMF-300, MMF-301, MMF-302, CMF-300, CRF-300) can operate in CLIP
mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are
also compatible with older 300 series devices. If a mix of old and new series devices are installed
on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC Wir-
ing Manual for a list of compatible addressable modules. Refer to the Device Compatibility Docu-
ment for a list of approved conventional notification and initiating devices.
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Transformer Assembly
One 100VA transformer is provided standard with the
panel (3.0 amps maximum for output circuits). An optional
100 VA transformer XRM-24B (XRM-24BE for the MS-
9200UDLSE) is available to provide maximum system and
accessory power (6.0 amps total). Note that the XRM-24B
and XRM-24BE are only suitable for use with MS-
9200UDLS(E) with a main circuit board assembly number
9200UDLS-PCX Rev Y, where "X" and "Y" can be any
Battery Cable P/N 75287
Product Description
19