Time-Out At Control Panel; Error Checking; Central Station Data Protection - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Remote Site Upload/Download

Time-out at Control Panel

Upon answering an incoming call on the primary Central Station phone line, the control panel will
listen for a modem connection signal. If this signal is not received within 50 seconds, the control
panel will disconnect the call. Upon successful connection (secret code verified), if no
communication occurs within 30 minutes, the panel will disconnect the call. Upon time-out,
transfer activity will be reported to the Central Station (if enabled) and the connection will be
terminated.

Error Checking

As each block of data is received by the control panel, it is checked for accuracy. If an error is
detected, the block is retransmitted until correct, up to a maximum of four times. If the Secret Code
is not verified and four errors occur, the call is disconnected and the report that the
upload/download was not successful is called to the Central Station(s).

Central Station Data Protection

The primary and secondary Central Station phone numbers, communications format, account code,
test time and programmable event codes are vital Central Station information. These blocks of data
are protected from partial programming due to faulty phone connections, line noise and other
errors. This prevents the panel from being confused due to a wrong phone number, account code,
test time and most critical formatting errors.
158
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014