Maintenance Programming Level - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Maintenance Programming Level

Pressing 1 while viewing the Program Check screen will display an NAC screen similar to the
PROGRAM CHECK
1=NACS NO INPUT
following.
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 and 67 but
no input devices have been programmed to any of these zones. Use the up and down arrow keys to
view all the NAC zones without input assignments for NAC 1, NAC2, NAC 3 and NAC 4.
Pressing 2 while viewing the Program Check screen will display a screen similar to the following:
The Zone No Input screen allows the programmer to view the zones which have not been
programmed to at least one input device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an
addressable module (control module in this example) with an address of 001 on loop 1 but have not
been programmed to any input devices. Use the up and down arrow keys to view all the zones
without input assignments.
Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be
displayed:
The Zone No Output feature allows the programmer to view the zones which have not been
programmed to at least one output device (not including general alarm Zone 00). The example in
the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an
addressable detector with an address of 001 on loop 1 but have not been programmed to any output
devices. Use the up and down arrow keys to view all the zones without output assignments.
3.7 Maintenance Programming Level
To access Maintenance Programming mode, press the Enter key. The LCD will display the
following:
To enter the Maintenance Programming mode, press 2. The display will read as follows:
When the Maintenance level password (default 11111) is entered, the following screen will appear:
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
NACS NO INPUT
NAC 1
25 31 44 55 67
ZONES NO INPUT
05 07 09 10 11 1M001
ZONES NO OUTPUT
05 07 09 10 11 1D001
1=READ STATUS
2=PROGRAMMING
3=REMOTE DOWNLOAD
PROGRAMMING
ENTER PASSWORD
PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK