Installation

2.8 Digital Communicator

Two independent telephone lines can be connected to the control panel. Telephone line con-
trol/command is made possible via double line seizure as well as usage of an RJ31X style intercon-
nection. Note that it is critical that the panel's digital communicator be located as the first device
on the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded.
Network
RJ31X
Service
Provider's
Facilities
Telephone
Line
Network
Demarcation
Point
The control panel's digital communicator is built into the main circuit board. Connection and wir-
ing of two phone lines is required as shown below.
KISSOFF
PRI. ACTIVE
J15
PRI. PHONE LINE
Male Plug
Connectors
38
Customer Premises Equipment and Wiring
Jack
FACP with DACT
Telephone
Answering
System
Figure 2.13 DACT Installation
SEC. ACTIVE
J16
Secondary
Phone Line
PH2
SEC. PHONE LINE
Module Female
Connectors
Figure 2.14 Wiring Phone Jacks
Unused
RJ-11 Jack
Fax Machine
Telephone
(Secondary Lines)
Incoming Telco Phone Lines
Green Wire
Ring
Tip
To premise phones
Red Wire
Ring
Tip
1 2 3 4 5 6
8
7
RJ31X
Jack
Note: Shorting
bars inside RJ31X
Jack removed
during installation.
7 foot Cable
MCBL-7
(ordered
separately)
Ferrite Clamps (see Section 2.8.1)
MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014
Digital Communicator
Computer
Telephone
Unused
RJ-11 Jack
Tip Green Wire
(Primary Lines)
Incoming Telco Phone Lines
Red Wire
Ring
Ring
To premise phones
Tip
1 2 3 4 5 6 7
8
RJ31X
Jack
Primary Phone
Line PH1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200udlseMs-9200udlsc

Table of Contents