Removing And Replacing The Power Supply Housing; Removing The Power Supply Housing - HP Integrity rx2660 User's & Service Manual

Hide thumbs Also See for Integrity rx2660:
Table of Contents

Advertisement

12. Align the alignment holes on the processor with the alignment posts on the processor cage,
and carefully lower the processor onto the processor socket. See
CAUTION:
pins seat into the socket. No additional pressure is required. Damage to the pins can occur
if pressure is applied.
13. Lock the processor into the socket on the processor board. See
a.
Unfasten the processor install tool (2.5 mm driver) from the tool holder on the airflow
guide.
b.
Insert the processor tool into the hole on the side of the heatsink.
c.
Rotate the processor tool clockwise 180 degrees.
CAUTION:
turning the processor tool half of a full turn. The counter-clockwise 180 degree rotation
(half turn) unlocks the socket. A clockwise 180 degree rotation locks the socket. Attempting
to turn the locking mechanism more than 180 degrees can severely damage the socket.
d.
Fasten the processor install tool (2.5 mm driver) to the tool holder on the airflow guide.
14. Connect the processor power cable into the connector cable that attaches directly to the
processor board. See
15. Close the processor cage. See
a.
Grasp the processor cage handle and rotate the cage closure inward toward the rear of
the assembly until it is completely closed.
b.
Apply adequate force to push the handle down until it is flush with the cage.
16. Replace the airflow guide. See
17. Replace the top cover.
18. If rack mounted, slide the server completely into the rack. See
Rack" (page
19. Reconnect the power cables and power on the server. See
the Server" (page
20. Verify processor replacement and operation by using the system utilities.
Use the iLO 2 MP SS command to verify operation
Use the EFI info cpu command to verify operation

Removing and Replacing the Power Supply Housing

The power supplies seat into a housing that attaches to the system board through the power supply
riser board.
WARNING!
the server prior to performing this procedure.
Voltages are present at various locations in the server whenever an AC power source is connected.
These voltages are present even when the main power switch is in the off position.
Failure to observe this warning can result in personal injury or damage to equipment.
CAUTION:
ESD safety precautions can result in damage to the server.

Removing the Power Supply Housing

To remove the power supply housing:
Do not press the processor into the socket. When properly aligned, the processor
The processor zero insertion force (ZIF) socket is locked and unlocked by
Figure
66.
"Replacing the Top Cover" (page
141).
77).
Ensure that the system is powered off and all power sources are disconnected from
Observe all ESD safety precautions before attempting this procedure. Failure to follow
Figure
65.
"Replacing the Airflow Guide" (page
Removing and Replacing the Power Supply Housing 177
Figure
67.
Figure
67.
145).
142).
"Inserting the Server into the
"Powering On and Powering Off