4-2 Function Mode

Binary Operation

•By allocating 02 to 05 (CF1 to CF4) to any of multi-function inputs 1 to 8 (C001 to C008), you can
select from multi-step speeds 0 to 15.
•Use A021 to A035 (multi-step speeds 1 to 15) to set frequencies for speeds 1 to 15.
•When the Digital Operator is selected as the frequency reference, speed 0 is set with A020/A220/
A320 or F001 (refer to page 4-8). When the control circuit terminal block is selected, speed 0 is set
with terminals O, O2, and OI.
Multi-step speeds
0th
1st
4
2nd
3rd
4th
5th
6th
7th
8th
9th
10th
11th
12th
13th
14th
15th
•For multi-step speed binary operation, you can set the wait time until which the terminal input is
determined in multi-step speed/position determination time C169. This prevents the transition status
before the input determination from being applied.
•If no input is made after the time set in C169, the data is determined.
(Note that the longer the determination time, the slower the input response.)
Without determination time (C169)
Frequency reference
4-17
CF4
CF3
CF2
CF1
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
15
11
9
1
CF1
CF2
CF3
CF4
4th
5th
3rd
6th
2nd
7th
1st
8th
CF1
CF2
CF3
CF4
FW
13
5
Determination
4
time (C169)
11th
10th
Frequency from
12th
the Digital Operator
9th
13th
or the external
analog input terminal
14th
15th
0th
With determination time (C169)