Omron RX User Manual page 84

200 v class three-phase input 0.4 to 55 kw; 400 v class three-phase input 0.4 to 132 kw
Hide thumbs Also See for RX:
Table of Contents

Advertisement

3-7 Parameter List
Parameter
Function name
No.
Integrated power
b078
clear
Integrated power
b079
display gain
b082
Starting frequency
3
b083
Carrier frequency
b084
Initialization selection
Initialization
b085
parameter selection
Frequency
b086
conversion coefficient
b087
STOP key selection
Free-run stop
b088
selection
Automatic carrier
b089
reduction
Usage rate of
b090
regenerative braking
function
b091
Stop selection
b092
Cooling fan control
Regenerative braking
b095
function operation
selection
Regenerative braking
b096
function ON level
b098
Thermistor selection
b099
Thermistor error level 0. to 9999.
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
3-35
Monitor or data range
Cleared with the Enter key after changing to
01
1. to 1000.
0.10 to 9.99
0.5 to 15.0 (0.4 to 55 kW)
*Derating enabled
0.5 to 10.0 (75 to 132 kW)
*Derating enabled
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes data
00
*Do not change.
0.1 to 99.0
00: Enabled
01: Disabled
02: Disabled only during stop
00: 0 Hz start
01: Frequency matching start
02: Active Frequency Matching restart
00: Disabled
01: Enabled
0.0 to 100.0
00: Deceleration → Stop
01: Free-run stop
00: Always ON
01: ON during RUN
00: Disabled
01: Enabled (Disabled during stop)
02: Enabled (Enabled during stop)
330 to 380
660 to 760
00: Disabled
01: PTC enabled
02: NTC enabled
Changes
Default
during
Unit
Page
setting
operation
00
Yes
1.
No
0.50
No
Hz
4-65
5.0
No
kHz
4-65
4-118
3.0
No
kHz
00
No
4-66
00
No
1.0
Yes
00
No
4-68
00
No
4-69
00
No
4-71
0.0
No
%
4-72
00
No
4-68
01
No
00
No
4-72
360/
No
V
720
00
No
4-73
Ω
3000.
No
4-4
4-2