200 v class three-phase input 0.4 to 55 kw; 400 v class three-phase input 0.4 to 132 kw
Hide thumbs Also See for RX:
Table of Contents

Advertisement

2-2 Wiring
Terminal
symbol
FW
2
1
2
3
4
5
6
7
8
CM1
11
12
13
14
15
CM2
AL2
AL1
AL0
2-9
Terminal name
Forward rotation
When the FW signal is ON, the motor runs
command terminal
forward. When it is OFF, the motor decelerates
and stops.
Multi-function input
Select 8 functions from among the 61 functions
and allocate them to terminals 1 to 8.
Note: Only terminals 1 and 3 can be used for the
Multi-function input
The sink and source logic for contact input can
common
be switched by connecting a short-circuit bar on
the control terminal block.
Short-circuiting P24 and PLC ⇒ Sink logic,
Short-circuiting PLC and CM1 ⇒ Source logic
To activate contact input via an external power
supply, remove the short-circuit bar and
connect CM1 terminal to the external interface
circuit.
Multi-function output
Select 5 functions from among 45, and allocate
them to terminals 11 through 15.
If an alarm code is selected in C062, terminals
11 to 13, or terminals 11 to 14 always output an
alarm factor code (e.g. Inverter trip). The signal
between each terminal and CM2 always
corresponds to the sink or source logic.
Multi-function output
Common terminals for multi-function output
common
terminals 11 to 15.
Relay output
Select the desired functions from among 45
functions, and allocate them. SPDT contact
output.
By factory default, the relay output (AL2, AL1)
contact selection (C036) is set at NC contact
between AL2-AL0, and NO contact between
Relay output
AL1-AL0.
common
Description
emergency shutoff function. For details,
refer to "Emergency Shutoff Function"
(page 2-10).
Specifications
[Contact input ON
condition]
Voltage between
each input terminal
and the CM1 terminal
:18 V DC or more
Input impedance
between each input
terminal and the CM1
terminal: 4.7 kΩ
Allowable max.
voltage:
Voltage between
each input terminal
and the CM1
terminal: 27 V DC
Load current at 27 V
DC power supply
voltage:
Approx. 5.6 mA
Between each
terminal and CM2
Voltage drop 4 V
max. at power-on
Max. allowable
voltage: 27 V DC
Max. allowable
current: 50 mA
Contact max.
capacity
AL2-AL0
250 V AC, 2 A
(Resistance)
0.2 A (Induction)
AL1-AL0
250 V AC, 1 A
(Resistance)
0.2 A (Induction)
Contact min. capacity
100 V AC, 10 mA
5 V DC, 100 mA
Continued to the next page