Omron RX User Manual page 339

200 v class three-phase input 0.4 to 55 kw; 400 v class three-phase input 0.4 to 132 kw
Hide thumbs Also See for RX:
Table of Contents

Advertisement

Note 1: For output voltage, use
a measurement device
that displays effective
values of fundamental
wave. For current and
electric power, use a
measurement device
that displays all
effective values.
Note 2: The Inverter output
waveform, under PWM
control, has a margin of
error, especially at a
low frequency.
Note 3: General-purpose
testers are not
applicable because of
noise in many cases.
Measurement Method of Output Voltage
R
R/L1
U/T1
S
Power supply
V/T2
S/L2
T
T/L3
W/T3
Diode
600 V 0.1 A min. (200-V class)
1000 V 0.1 A min. (400-V class)
Effective value of fundamental wave VAC
V
= 1.1 × V
AC
DC
6-1 Inspection and Maintenance
U
V
Motor
W
2 W 220 kW
+
V
DC
Moving coil type
300 V (200-V class)
-
600 V (400-V class)
6
6-10

Hide quick links:

Advertisement

Table of Contents
loading