200 v class three-phase input 0.4 to 55 kw; 400 v class three-phase input 0.4 to 132 kw
Hide thumbs Also See for RX:
Table of Contents

Advertisement

4-2 Function Mode
Specifications of Multi-function Output Terminals 11 to 15
•Below are the specifications of multi-function output terminals 11 to 15.
C031 to C035 set values
4
Specifications of the Relay Output Terminals
•The relay output terminals have an SPDT contact configuration. Below is its operation.
(Example) When the relay output terminals are used for alarm
C036
set
Power
values
ON
00
OFF
ON
01
(Default)
OFF
4-95
15
Inside the Inverter
Power
supply
ON
00
(NO contact)
OFF
ON
01
(NC contact)
OFF
Inside the Inverter
Output terminal
status
Inverter
status
AL2-
AL1-
AL0
AL0
Abnormal
Closed
Open
Normal
Open
Closed
Open
Closed
Abnormal
Open
Closed
Normal
Closed
Open
Open
Closed
CM2
11
Output
Electrical characteristics
status
ON
Between each terminal and CM2
Voltage drop 4 V max. at power-on
OFF
Max. allowable voltage: 27 V DC
Max. allowable current: 50 mA
ON
OFF
AL0
AL2
AL1
(Default value: C036 = 01)
Resistance load
Max.
250 V AC, 2 A
contact
30 V DC, 8 A
capacity
AL2-
AL0
Min.
contact
capacity
Max.
250 V AC, 1 A
contact
30 V DC, 1 A
capacity
AL1-
AL0
Min.
contact
capacity
Inductive load
250 V AC, 0.2 A
30 V DC, 0.6 A
100 V AC, 10 mA
5 V DC, 100 mA
250 V AC, 0.2 A
30 V DC, 0.2 A
100 V AC, 10 mA
5 V DC, 100 mA