200 v class three-phase input 0.4 to 55 kw; 400 v class three-phase input 0.4 to 132 kw
Hide thumbs Also See for RX:
Table of Contents

Advertisement

2-2 Wiring
Arrangement of Main Circuit Terminals
The terminal arrangement on the Inverter main circuit terminal block is shown below.
2
Ro
CHARGE LED indicator
PD/+1 - P/+ short-circuit bar
[EMC filter function switching method]
Filter disable pin (J62)
EMC filter disabled
EMC filter enabled (factory default)
R/L1
S/L2
G
Ground terminal with short-circuit
bar (shaded area) for EMC filter
function switching
[EMC filter function switching method]
EMC filter enabled (factory default)
2-15
Terminal arrangement
R/L1
S/L2
T/L3
To
PD/+1
P/+
In order to enable the EMC filter
Dummy plug
function, set up the plug inserted
(green)
into the filter enable pin (J61) and
filter disable pin (J62) as shown in
the table below. Confirm that
electrical power has been
disconnected before performing this
Filter enable pin
setup. Not doing so may result in
(J61)
electric shock. Also, use with the
plug inserted.
Short plug
Filter enable pin (J61)
Dummy plug (green)
Short plug
CHARGE LED indicator
T/L3
PD/+1
P/+
N/-
PD/+1 - P/+
short-circuit bar
When not using the DC
reactor, keep the PD/+1 - P/+
short-circuit bar attached.
U/T1
V/T2
W/T3
G
G
RB
N/-
When not using the DC reactor,
keep the PD/+1 - P/+ short-circuit bar
attached.
Filter disable pin (J62)
Short plug
Dummy plug (green)
Ro
To
RB
U/T1
V/T2
W/T3
G
EMC filter disabled
Applicable model
RX-A2004 to A2037
RX-A4004 to A4037
Ro,To: M4
Ground terminal: M4
Others: M4
RX-A2055, A2075
RX-A4055, A4075
Ro,To: M4
Ground terminal: M5
Others: M5
RX-A2110
RX-A4110
Ro,To: M4
Ground terminal: M6
Others: M5