Omron RX User Manual page 290

200 v class three-phase input 0.4 to 55 kw; 400 v class three-phase input 0.4 to 132 kw
Hide thumbs Also See for RX:
Table of Contents

Advertisement

4-4 Communication Function
Register
No.
Operation frequency input
12AFh
A setting
4
Operation frequency input
12B0h
B setting
12B1h
Operator selection
12B2h
Not used
12B3h
Frequency addition
amount
12B4h
Frequency addition
12B5h
direction
12B6h
to
Not used
12B8h
EL-S-curve ratio 1 during
12B9h
acceleration
EL-S-curve ratio 2 during
12BAh
acceleration
EL-S-curve ratio 1 during
12BBh
deceleration
EL-S-curve ratio 2 during
12BCh
deceleration
12BDh
to
Not used
1300h
1301h
Retry selection
Allowable momentary
1302h
power interruption time
1303h
Retry wait time
Momentary power
1304h
interruption/undervoltage
trip during stop selection
4-185
Function
Function name
code
A141
A142
A143
A145
(HIGH)
A145
(LOW)
A146
A150
A151
A152
A153
b001
b002
b003
b004
R/W
Monitor and setting parameters
0: Digital Operator (F001)
1: Digital Operator (FREQ adjuster)
2: Input O
3: Input OI
R/W
4: RS485 communication
5: Option 1
6: Option 2
7: Pulse train frequency
0: Digital Operator (F001)
1: Digital Operator (FREQ adjuster)
2: Input O
3: Input OI
R/W
4: RS485 communication
5: Option 1
6: Option 2
7: Pulse train frequency
0: Addition (A + B)
R/W
1: Subtraction (A - B)
2: Multiplication (A × B)
R/W
0 to 40000
R/W
0: Frequency reference + A145
R/W
1: Frequency reference - A145
R/W
0 to 50
R/W
0 to 50
R/W
0 to 50
R/W
0 to 50
0: Trip
1: 0-Hz start
2: Frequency matching start
R/W
3: Trip after frequency matching
deceleration stop
4: Active Frequency Matching restart
R/W
3 to 250
R/W
3 to 1000
0: Disabled
1: Enabled
R/W
2: Disabled during stop and deceleration
stop
Resolution
0.01 [Hz]
1 [%]
1 [%]
1 [%]
1 [%]
0.1 [s]
0.1 [s]