Omron RX User Manual page 287

200 v class three-phase input 0.4 to 55 kw; 400 v class three-phase input 0.4 to 132 kw
Hide thumbs Also See for RX:
Table of Contents

Advertisement

Register
Function name
No.
Startup DC injection
124Ch
braking time
DC injection braking
124Dh
carrier frequency
124Eh
Not used
124Fh
Frequency upper limit
1250h
1251h
Frequency lower limit
1252h
1253h
Jump frequency 1
1254h
1255h
Jump frequency width 1
1256h
Jump frequency 2
1257h
1258h
Jump frequency width 2
1259h
Jump frequency 3
125Ah
125Bh
Jump frequency width 3
125Ch
Acceleration stop
frequency
125Dh
125Eh
Acceleration stop time
125Fh
PID selection
1260h
PID P gain
1261h
PID I gain
1262h
PID D gain
1263h
PID scale
1264h
PID feedback selection
1265h
Reverse PID function
Function
R/W
Monitor and setting parameters
code
A058
R/W
0 to 600
5 to 150 (0.4 to 55 kW)
A059
R/W
5 to 100 (75 to 132 kW)
A061
R/W
(HIGH)
0/Frequency lower limit to
Max. frequency
A061
R/W
(LOW)
A062
R/W
(HIGH)
0/Starting frequency to
Frequency upper limit
A062
R/W
(LOW)
A063
R/W
(HIGH)
0 to 40000
A063
R/W
(LOW)
A064
R/W
0 to 1000
A065
R/W
(HIGH)
0 to 40000
A065
R/W
(LOW)
A066
R/W
0 to 1000
A067
R/W
(HIGH)
0 to 40000
A067
R/W
(LOW)
A068
R/W
0 to 1000
A069
R/W
(HIGH)
0 to 40000
A069
R/W
(LOW)
A070
R/W
0 to 600
0: Disabled
A071
R/W
1: Enabled
2: Reverse output enabled
A072
R/W
2 to 50
A073
R/W
0 to 36000
A074
R/W
0 to 10000
A075
R/W
1 to 9999
0: Input OI
1: Input O
A076
R/W
2: RS485 communication
3: Pulse train frequency
10: Operation function output
0: Disabled
A077
R/W
1: Enabled
4-4 Communication Function
Resolution
0.1 [s]
0.1 [kHz]
0.01 [Hz]
4
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.01 [Hz]
0.1 [s]
0.1
0.1 [s]
0.01 [s]
0.01