4-2 Function Mode
(Example 1)
Main circuit P-N voltage
Vpn (V)
Output
frequency
4
(Hz)
Note: The main circuit DC voltage level, while the function is running, may fall below the b052 set value depending
Window Comparator (Disconnection Detection ODc/OIDc/O2Dc)
•The Inverter activates the window comparator output when the O/OI/O2 analog input value is
within the upper and lower limit levels of the window comparator. This function allows you to
monitor analog input based on the desired level (e.g. to detect a disconnection).
Parameter No.
C021 to C025
C026
b060 (O)
b063 (OI)
b066 (O2)
b061 (O)
b064 (OI)
b067 (O2)
4-63
Power recovery
Main circuit DC voltage
DC voltage kept constant
b050 = 02, 03
(Deceleration stop)
Power recovery
on the proportional gain and integral time settings.
Function name
Multi-function output
27: ODc (analog O disconnection detection)
terminals 11 to 15
28: OIDc (analog OI disconnection detection)
selection
29: O2Dc (analog O2 disconnection
54: WCO (window comparator O)
Relay output (AL2, AL1)
55: WCOI (window comparator OI)
function selection
56: WCO2 (window comparator O2)
Set an upper limit level.
Window comparator
O/OI/O2 upper limit level
Set an upper limit level.
Set a lower limit level.
Window comparator
O/OI/O2 lower limit level
Set a lower limit level.
(Example 2)
Main circuit P-N voltage
Vpn (V)
b052
b051
Time
Output
frequency
(Hz)
Time
Data
detection)
Setting range: 0 to 100
Lower limit: Lower limit level + Hysteresis
width × 2
Setting range: -100 to 100
Lower limit: Lower limit level + Hysteresis
width × 2
Setting range: 0 to 100
Upper limit: Upper limit level - Hysteresis
width × 2
Setting range: -100 to 100
Upper limit: Upper limit level - Hysteresis
width × 2
Main circuit DC voltage
at power recovery
DC voltage kept constant
b050 = 03 (Operation)
b050 = 02
(Deceleration stop)
Power recovery
Default setting
05
100
0
-100
b052
b051
Time
Time
Unit
%
%
%