Parameter
Function name
No.
Overload limit
b021
selection
b022
Overload limit level
Overload limit
b023
parameter
Overload limit
b024
selection 2
b025
Overload limit level 2
Overload limit
b026
parameter 2
Overcurrent
b027
suppression function
Active Frequency
b028
Matching restart level
Active Frequency
b029
Matching restart
parameter
Starting frequency at
b030
Active Frequency
Matching restart
b031
Soft lock selection
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
Monitor or data range
00: Disabled
01: Enabled in acceleration/constant speed
operation
02: Enabled in constant speed operation
03: Enabled in acceleration/constant speed
operation (Accelerates during
regeneration)
0.20 × Rated current to 2.00 × Rated current
(0.4 to 55 kW)
0.20 × Rated current to 1.80 × Rated current
(75 to 132 kW)
0.10 to 30.00
00: Disabled
01: Enabled in acceleration/constant speed
operation
02: Enabled in constant speed operation
03: Enabled in acceleration/constant speed
operation (Accelerates during
regeneration)
0.20 × Rated current to 2.00 × Rated current
(0.4 to 55 kW)
0.20 × Rated current to 1.80 × Rated current
(75 to 132 kW)
0.10 to 30.00
00: Disabled
01: Enabled
0.20 × Rated current to 2.00 × Rated current
(0.4 to 55 kW)
0.20 × Rated current to 1.80 × Rated current
(75 to 132 kW)
0.10 to 30.00
00: Frequency at interruption
01: Max. frequency
02: Set frequency
00: Data other than b031 cannot be changed
when terminal SFT is ON.
01: Data other than b031 and the specified
frequency parameter cannot be changed
when terminal SFT is ON.
02: Data other than b031 cannot be changed.
03: Data other than b031 and the specified
frequency parameter cannot be changed.
10: Data other than parameters changeable
during operation cannot be changed.
Appendix-1 Parameter List
Changes
Default
during
Unit
setting
operation
01
No
1.50
×
No
A
Rated
current
1.00
No
s
01
No
1.50
×
No
A
Rated
current
1.00
No
s
01
No
Rated
No
A
current
0.50
No
s
00
No
01
No
App-14
Page
4-49
4-51
4-43
4-69
4-51