Omron RX User Manual page 388

200 v class three-phase input 0.4 to 55 kw; 400 v class three-phase input 0.4 to 132 kw
Hide thumbs Also See for RX:
Table of Contents

Advertisement

Appendix-1 Parameter List
Parameter
Function name
No.
Window comparator
b060
O upper limit level
Window comparator
b061
O lower limit level
Window comparator
b062
O hysteresis width
Window comparator
b063
OI upper limit level
Window comparator
b064
OI lower limit level
Window comparator
b065
OI hysteresis width
Window comparator
b066
O2 upper limit level
Window comparator
b067
O2 lower limit level
Window comparator
b068
O2 hysteresis width
Analog operation
b070
level at O
disconnection
Analog operation
b071
level at OI
disconnection
Analog operation
b072
level at O2
disconnection
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.
App-17
Monitor or data range
Set an upper limit level.
Setting range: 0 to 100
Lower limit: Lower limit level + Hysteresis
width × 2
Set a lower limit level.
Setting range: 0 to 100
Upper limit: Upper limit level - Hysteresis
width × 2
Set a hysteresis width for the upper and lower
limit levels.
Setting range: 0 to 10
Upper limit: (Upper limit level - Lower limit
level) × 2
Set an upper limit level.
Setting range: 0 to 100
Lower limit: Lower limit level + Hysteresis
width × 2
Set a lower limit level.
Setting range: 0 to 100
Upper limit: Upper limit level - Hysteresis
width × 2
Set a hysteresis width for the upper and lower
limit levels.
Setting range: 0 to 10
Upper limit: (Upper limit level - Lower limit
level) × 2
Set an upper limit level.
Setting range: -100 to 100
Lower limit: Lower limit level + Hysteresis
width × 2
Set a lower limit level.
Setting range: -100 to 100
Upper limit: Upper limit level - Hysteresis
width × 2
Set a hysteresis width for the upper and lower
limit levels.
Setting range: 0 to 10
Upper limit: (Upper limit level - Lower limit
level) × 2
0. to 100./no (ignored)
0. to 100./no (ignored)
-100. to 100./no (ignored)
Changes
Default
during
Unit
Page
setting
operation
100.
Yes
%
0.
Yes
%
0.
Yes
%
100.
Yes
%
4-63
0.
Yes
%
0.
Yes
%
100.
Yes
%
-100.
Yes
%
0.
Yes
%
4-63
no
No
no
No
no
No

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents