4-4 Communication Function
<Writing Into the Holding Register [06h]>
Writes data into the specified holding register.
(Example)
Write 50 Hz into the Inverter with slave address 5 as the base frequency (A003).
The data resolution of the holding register "1203h" of the base frequency (A003) is 1 Hz. To set 50
Hz, set the change data to "50 (0032h)".
Query
No.
1
Slave address
4
2
Function code
3
Register start number (MSB)
4
Register start number (LSB)
5
Change data (MSB)
6
Change data (LSB)
7
CRC-16 (MSB)
8
CRC-16 (LSB)
*1. There is no response for broadcasting.
*2. Note that the start number is reduced by 1.
If writing into the holding register cannot be performed normally, refer to the "Exception Response"
section.
<Loop-back Test [08h]>
Used to check the communications between master and slave. A random value can be used for test
data.
(Example)
Loop-back test to the Inverter with slave address 1
Query
No.
Field name
1
Slave address
2
Function code
3
Diagnostic sub code (MSB)
4
Diagnostic sub code (LSB)
5
Data (MSB)
6
Data (LSB)
7
CRC-16 (MSB)
8
CRC-16 (LSB)
* Broadcasting cannot be performed.
The diagnostic sub code corresponds only with the query data echo (00h, 00h), not any other
commands.
4-165
Example
Field name
(HEX)
*1
*2
*2
Example
(HEX)
*
01
08
00
00
Random
Random
CRC
CRC
Response
No.
05
1
Slave address
06
2
Function code
12
3
Register start number (MSB)
02
4
Register start number (LSB)
00
5
Change data (MSB)
32
6
Change data (LSB)
AD
7
CRC-16 (MSB)
23
8
CRC-16 (LSB)
Response
No.
1
Slave address
2
Function code
3
Diagnostic sub code (MSB)
4
Diagnostic sub code (LSB)
5
Data (MSB)
6
Data (LSB)
7
CRC-16 (MSB)
8
CRC-16 (LSB)
Example
Field name
(HEX)
05
06
12
02
00
32
AD
23
Example
Field name
(HEX)
01
08
00
00
Random
Random
CRC
CRC