Frequency Reference Setting Selection - Omron SYSDRIVE 3G3HV SERIES User Manual

High-capacity general-purpose inverter
Hide thumbs Also See for SYSDRIVE 3G3HV SERIES:
Table of Contents

Advertisement

Preparing for Operation
Note Press the Operation Mode Selection Key to control the Inverter from the Digital Operator with the
run command and frequency reference if n007 is set to 1. The operation mode selected with n002
will be valid if the Operation Mode Selection Key is pressed again.
n008
Stop Key Function Selection
Setting range
0, 1
• Set n008 so that the STOP/RESET Key will function properly.
Set Values
Set value
0
The STOP/RESET Key will function only when the Inverter is running with the run command
through the Digital Operator.
1
The STOP/RESET Key will function anytime.
n009

Frequency Reference Setting Selection

Setting range
0, 1
• Select with n009 a method to set a frequency reference with the Digital Operator.
Set Values
Set value
0
Permits the frequency reference set with the Digital Operator to be valid without the Enter Key.
1
Permits the frequency reference set with the Digital Operator to be valid with the Enter Key.
Note A frequency reference will be valid the moment the frequency reference is set with the Digital Op-
erator if n009 is set to 0.
n010
V/f Pattern Selection
Setting range
0 to F
Set Values
• The following two methods are available to set the V/f pattern.
S Select one of the 15 V/f patterns preset with the Inverter, in which case set n010 to 0, 1, 2, 3, 4, 5, 6,
7, 8, 9, A, b, C, d, or E.
S Set n010 to F for an optional V/f pattern.
3-58
Unit
---
Description
Unit
---
Description
Unit
---
Chapter 3
Default setting
1
Default setting
1
Default setting
1