Omron CX-INTEGRATOR - V2.3 REV 02-2009 Operation Manual page 203

Table of Contents

Advertisement

4-3
Manually Setting Data Links
4-3-4
Creating Data Link Tables Offline
No.
(1)
Node
(2)
PLC
(3)
Memory area
(4)
Start Address
(5)
Size
(6)
Status
(7)
Ordered Destination
Nodes
(8)
Make Default
(9)
Next >>
Note: The default setting for data link status depends on the PLC being used. For details, refer
PLC
CS/CJ Series
7 Set node address 01 as shown in the following table, and then click the Next Button
4-14
Item
Displays node address to set.
Sets the PLC type.
Area 1 memory area
Area 2 memory area
Area 1 start address
Area 2 start address
Area 1 local node send size (in words)
Area 2 local node send size (in words)
Data link status memory area (See note.)
Node Refresh Sequence
Beginning with the data link start address above, specify which nodes
are to have data refreshed at the local node address and the order in
which data is to be refreshed (i.e., the node refresh sequence). This
order will be the same for Area 1 and Area 2.
(For the local node address, data is sent from the local node area. For a
remote node address, data is received from the remote node address to
the local area.)
Note:
• The local node must be included in the refresh nodes.
• If the address of any node participating in the data links is not entered
here, data will not be received from that node.
Example: If 1, 2, 3 is input, node addresses 1, 2, and 3 will be allocated
in order, beginning with the start address.
Click this button to make the values set for the above items the default
values for new data link settings.
Click to proceed to the next dialog box.
to the Controller Link Units Operation Manual (W309).
The data link status is contained in the 16 words (fixed) from CIO 1500 + 25 × unit
number + 7 to 22 in the CPU Bus Unit Area.
15
8 7
+7 words
Node 2
...
...
+22 words
Node 32
or press the Enter key. Set node addresses 02 and 03 in the same way.
Item
Node address
PLC type
Area 1
Memory area
Start address
Send size
Area 2
Memory area
Start address
Send size
Ordered destination nodes
Status
Memory area
Start address
Function
Data link status
0
Node 1
...
Node 31
Data set
1
CS1G-CPU45
CIO
1000
30
D
500
30
1, 2, 3
CIO
1100
Description
Sets CIO 1000 as the data link start
address for the Area 1 local node.
Sets 30 words as the send size (unit:
words) for the Area 1 local node.
Sets D00500 as the data link start
address for the Area 2 local node.
Sets 30 words as the send size (unit:
words) for the Area 2 local node.
Specifies the node refresh sequence.
Beginning with the start addresses,
nodes 01, 02, and 03 are set in order.
(The local node address is 1, so
transmission is first, followed by
reception from node 02, and finally
reception from node 03.)
Sets CIO 1100 as the data link status
start address.