10 CPU Unit Functions

10-8-4 Synchronous Data Refresh

The Synchronous Data Refresh Area in the CIO Area of the CPU Unit always starts at CIO 1200. The
output data sent from the CPU Unit to Synchronous Units is first and is followed by the input data sent
from the Synchronous Units to the CPU Unit.
Synchronous
output data
(Contains
commands and
other data for
Synchronous
Units.)
Synchronous
input data
(Contains
present values
and other
information from
Synchronous
Units.)
The following settings are made in the Synchronous Unit Operation Settings Area of the Timings/Syn-
chronous Tab Page in the PLC Setup.
• The total size of the output data and the total size of the input data
• The output size and input size for each Unit
• The start address of input area
10-88
CPU Unit
I/O memory
Synchronous Data Refresh
Area
CIO 1200
CPU Unit (8 words)
CIO 1202
Synchronous
Unit 1 (8 words)
CIO 1210
Synchronous
Unit 2 (8 words)
CIO 1250
Synchronous
Unit 1 (8 words)
CIO 1258
Synchronous
Unit 2 (8 words)
Words allocated to CPU Unit
(Used, for example, for command
information to stop all axes.)
Synchronous Unit 1
CPU Unit (8 words)
Synchronous
Unit 1 (8 words)
Synchronous
Unit 1 (8 words)
CJ2 CPU Unit Software User's Manual
Synchronous Unit 2
CPU Unit (8 words)
Synchronous
Unit 2 (8 words)
Synchronous
Unit 2 (8 words)