Usage
• The system can be configured so that a PLC can be written only from authorized nodes in the net-
work. (For example, use this function when the system's control/monitoring computer is the only
node allowed to write to a Controller within a piece of equipment.)
By limiting the number of nodes that can write to the PLC, it is possible to prevent system prob-
lems caused by unintentional overwrites during data monitoring.
Operations Restricted by Network FINS Write Protection
FINS Write Commands
The following FINS commands are restricted by FINS write protection when sent to the CPU Unit
through the network.
Code
0102 hex
MEMORY AREA WRITE
0103 hex
MEMORY AREA FILL
0105 hex
MEMORY AREA TRANSFER
0202 hex
PARAMETER AREA WRITE
0203 hex
PARAMETER AREA FILL (CLEAR)
0307 hex
PROGRAM AREA WRITE
0308 hex
PROGRAM AREA CLEAR
0401 hex
RUN
0402 hex
STOP
0702 hex
CLOCK WRITE
0C01 hex
ACCESS RIGHT ACQUIRE
CJ2 CPU Unit Software User's Manual
System control/monitoring computer
Equipment
Network
Controller
Monitoring computer
Allowed to
write/
control PLC
Network
Network
CS/CJ
CS/CJ
Command name
10 CPU Unit Functions
Allowed to
write/control PLC
Not allowed to
write/control PLC
Code
Command name
2101 hex
ERROR CLEAR
2103 hex
ERROR LOG POINTER CLEAR
2203 hex
SINGLE FILE WRITE
2204 hex
FILE MEMORY FORMAT
2205 hex
FILE DELETE
2207 hex
FILE COPY
2208 hex
FILE NAME CHANGE
220A hex
MEMORY AREA-FILE TRANSFER
220B hex
PARAMETER AREA-FILE TRANSFER
220C hex
PROGRAM AREA-FILE TRANSFER
2215 hex
CREATE/DELETE DIRECTORY
2301 hex
FORCED SET/RESET
2302 hex
FORCED SET/RESET CANCEL